EtherTRAK ®2 and Etherbus ®Dual Ethernet I/O Module5.2.6 TABLE F Modules 16ISOTCUpper Row Lower RowTerm # Function Term # Function1 Earth 11 AX0 – TC 1 (+)2 PWR GND 12 AX0 – TC 1 (-)3 PWR 13 AX1 – TC 2 (+)4 PWR2 14 AX1 – TC 2 (-)5 PWR OUT+ 15 AX2 – TC 3 (+)6 WATCHDOG 16 AX2 – TC 3 (-)7 RS485 + 17 AX3 – TC 4 (+)8 RS485 - 18 AX3 – TC 4 (-)9 RS485 Term 19 AX4 – TC 5 (+)10 RS485 GND 20 AX4 – TC 5 (-)21 AX5 – TC 6 (+)22 AX5 – TC 6 (-)23 AX6 – TC 7 (+)24 AX6 – TC 7 (-)25 AX7 – TC 8 (+)26 AX7 – TC 8 (-)27 AX8 – TC 9 (+)28 AX8 – TC 9 (-)29 AX9 – TC 10 (+)30 AX9 – TC 10 (-)31 AX10 – TC 11 (+)32 AX10 – TC 11 (-)33 AX11 – TC 12 (+)34 AX11 – TC 12 (-)35 AX12 – TC 13 (+)36 AX12 – TC 13 (-)37 AX13 – TC 14 (+)38 AX13 – TC 14 (-)39 AX14 – TC 15 (+)40 AX14 – TC 15 (-)41 AX15 – TC 16 (+)42 AX15 – TC 16 (-)Note – The screw terminals used on the E2-BASE-TC-1(used in E2-16ISOTC-D only) can accept 30 to 16 AWG. The screwsize is M2 and the recommended torque is 1.5 IN/LB.ToPanel10 - 30 VDCUser PowerGND++- ToRS485DevicePhone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com