EtherTRAK®2 and Etherbus®Dual Ethernet I/O Module5.2.1 TABLE A Modules E2/EB-MIX24880 and MIX24882Module E2/EB-MIX24880-D and E2/EB-MIX24882-D screw terminal assignment.Upper Row Lower RowTerm # Function Term # Function11 X0 – Din 1 12 X1 – Din 213 X2 – Din 3 14 X3 – Din 415 X4 – Din 5 16 X5 – Din 617 X6 – Din 7 18 X7 – Din 819 X8 – Din 9 20 X9 – Din 1021 X10 – Din 11 22 X11 – Din 1223 X12 – Din 13 24 X13 – Din 1425 X14 – Din 15 26 X15 – Din 1627 *X16 – Din 17, Y0 – Dout 1 28 *X17 – Din 18, Y1 – Dout 229 *X18 – Din 19, Y2 – Dout 3 30 *X19 – Din 20, Y3 – Dout 431 *X20 – Din 21, Y4 – Dout 5 32 *X21 – Din 22, Y5 – Dout 633 *X22 – Din 23, Y6 – Dout 7 34 *X23 – Din 24, Y7 – Dout 835 AX0 – Ain 1 36 AX1 – Ain 237 AX2 – Ain 3 38 AX3 – Ain 439 AX4 – Ain 5 40 AX5 – Ain 641 AX6 – Ain 7 42 AX7 – Ain 843 AY0 (MIX24882 only) orCNT0+ which is read as AX8(MIX24880 only)44 AY1 (MIX24882 only) or CNT0- readas AX8 (MIX24880 only)Note: The counter input is anisolated differential pair.)* Specifically in the E2-MIX2480 and E2-MIX24882, power to I/O module and power to combination discreteinputs/outputs should be from the same power source. See the Combination DI/DO in section 6 for more information.(sourcing orsinking DI)4-20 mA AI(Loop poweredAI shown)(sourcing DI orDO; DO shown)4-20 mA AOor CNT -4-20 mA AI(Loop poweredAI shown)4-20 mA AOor CNT +(sourcing orsinking DI)(sourcing DI orDO; DO shown)_ + _ +_+_+Ref DIN5.1KJumperJumperRef DINDC Power +Return -5.1KSinking Input SwitchSourcing Input SwitchEquivalentDC Input CircuitsReturn -DC Power +_+ 100ohmsAINEquivalent AnalogInput Circuit(4-20 mA)AOUT +DC+Equivalent AnalogOutput Circuit(4-20 mA)Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com