EtherTRAK®2 and Etherbus®Dual Ethernet I/O Module1.2.14 E2/EB-16ISOTC-D SpecificationsAnalog Input ChannelsAnalog Input Ranges: +/-250 mV, Thermocouples supported J,K,E,R,T,B,L,N & SA/D resolution 16 bits (0.003%)Full scale accuracy +/- 0.02% (at 20 °C, 16 bit mode)Temperature coefficient +/- 50 ppm per °C (span and offset)Input impedance (resistance): 200 KohmsDMRR (differential mode) 66 db at 50/60 HzFastest update time (all 16 channels): 200 msAccuracy typical uncalibrated +/- 0.5 °CCommon mode input voltage: Between two input terminals +/- 60VDCBetween inputs and ground 300 volts1.2.15 E2/EB-10RTD-D SpecificationSerial PortsRS485 port, Screw terminals (485+, 485-, GND) (2-wire half-duplex, isolated)Isolations voltage, 150VRS485 networking, Up to 32 (full-load) stationsRS485 distance, Up to 0.5 miles (baud rate dependent)Baud Rates from 150 to 57,600 baudProtocols: master and slave: Sixnet and Modbus RTU / ASCIIDiagnostic LEDs: Transmit (TD) and Receive (RD)Analog Input ChannelsRTD input range: -200-850 deg CRTD overall accuracy: .05% or .5 deg CA/D resolution 16 bits (0.003%)Temperature coefficient +/- 50 ppm per °C (span and offset)RTD Type: 100 Ohm PlatinumRTD Alpha: .00385 or .00392RTD Connections: 2 or 3-wireScan time: 550 ms for all 10 channelsMax lead wire resistance: 100 Ohms per side balancedRTD excitation current: 250uA pulsed to reduce self-heatingPhone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com