1Programmable MonitoringThe G3 has an extensive monitoring system which is employed via the keypad. The informationgiven in the monitor displays is useful while troubleshooting or commissioning applications.Key Display DescriptionMOTOR RUN DIRECTION:FORWARDIndicates direction associated with speed reference. Keypad direction referenceis separate from terminal strip direction reference.MONITOR #1MONITOR #2PROGRAMMABLEMONITOR #3 SEE BELOWMONITOR #4STATUS: R:-- S1:-- S2:--S3:-- S4:-- S5:--As these input terminals are shorted to CC, the “--” will change to “ON”. Usethis as a troubleshooting tool.ST:ON F:-- RES:--S6:-- S7:-- S8:--As these input terminals are shorted to CC, the “--” will change to “ON”. Usethis as a troubleshooting tool. S6, S7, and S8 exist only on option card.RCH:-- LOW:-- FLT:--OUT:-- FAN:-- MC:ONAs these output terminals close, the “--” will change to “ON”. Use this as atroubleshooting tool. OUT exists only on option card. MC always says “ON”.“FAN” shows “ON” when the drive’s muffin fan is on.CUMULATIVE RUN TIME0.00.01 represents one hour. The timer is not resettable. An output contact can beprogrammed to change state based on the CRT.PAST TRIP #1NO ERRORPAST TRIP #2NO ERRORThe drive stores past faults; to clear these, put a “4” into Standard Setting ModeSelection in the UTILITY PARAMETERS group.PAST TRIP #3NO ERRORPAST TRIP #4NO ERRORMOTOR RUN DIRECTION:FORWARDEnd/beginning of MONITOR mode* For additional assistance, please contact Toshiba Adjustable Speed Drive Marketing Dept. at (800) 872-21924