52 43-TV-25-35 GLO Iss.4 Dec 06 UKA5E01001767-04Power upAnalogue In Menu(Main Menu > Configure > Setup > Edit Setup> Field IO > Analogue In)Press the Analogue In button to display all the analogue inputs available.Click on individual Analogue In number to set up each channel profile. Each channel has alist of menu items to be configured.Refer to connection details and “Analogue Input Channel Numbers” on page 17..• Enabled - Toggle On and Off.• Type - Select this for a list of available Signal Inputs.• Sample Rate - Select this for a list of available Analogue Input sample speeds. A FastScanning range of 50Hz (20ms) is available as a firmware option (not available for theSIREC D200 recorder) . See “Firmware Credit System” on page 167.Arranged in 2 banks of 3 inputs, and sample rate must be the same within each bank,only for SIREC D200 recorder.• Range (Ohms, Volts and Amps only) - Toggle between Preset and User Defined. ThePreset option will make available a list of Range Types or select User Defined to specifyHigh and Lower Limits.• Range Type (Ohms, Volts and Amps only) - Only available when Range is set to Pre-set. Select for a list of available ranges. The factory default range is +/-12V. See“User Defined Maximum Input Ranges” on page 220• Damp Level - The damping filter is an advanced algorithm offering improved responseover more traditional methods. It works by producing configuable levels of damping -but at the same time being able to respond rapidly to large input changes. Enter theDamp Level in Engineering Units.The Analogue In screendisplays all the availableAnalogue Input channels.Each channel displays its’individual settings.Select a numbered chan-nel to edit the configura-tion of each inputMenu path to current menu