5. Parameters 5-555.7.4 Multi-function analog output : H3.01~H3.035.7.4.1 Setting multi-function analog output : H3.01ParameterNo. Name Unit SettingrangeFactorySettingChangeableduringoperationH3.01 Analog MonitorFunction Setting - 0~7 1• H3.01 is used to select the function of the analog monitor outputterminal.• SettingSettingconstant Function Reference0 Frequency command U0.011 Output frequency U0.022 Output current U0.033 Output voltage U0.044 DC voltage U0.055 Output power U0.066 Motor speed U0.077 Estimated torque U0.085-56 MOSCON-E7 User’s Manual5.7.4.2 Adjusting the monitor output : H3.02, H3.03ParameterNo. Name Unit Settingrange FactorySettingChangeableduringoperationH3.02 Analog MonitorGain setting 0.1% 0.0~200.0 100.0 OH3.03 Analog MonitorBias setting 0.1% -100.0~100.0 0.0 O• H3.02 and H3.03 are used to set the gain and bias of monitor output.• H3.02 : set what multiple of 10V will correspond to a 100% output ofthe monitored item.• H3.03: set the amount that the output characteristic will be shiftedvertically. Set this amount as a percentage, with 10V corresponding to100%.Figure 5.23 Monitor output adjustmentsAnalog outputMax. Output Frequency Gain100Max. Output Frequency Bias1000V 10VUse the current value in parenthesiswhen current input has been selectedWhen H3.01=0FrequencyCommand