5. Parameters 5-535.7.3.3 Adjusting analog inputs : H2.03, H2.04, H2.06, H2.07ParameterNo. Name Unit Settingrange FactorySettingChangeableduringoperationH2.03 Voltage InputGain(Terminal 9)0.1% 0.0~200.0 100.0 OH2.04 Voltage InputBias(Terminal 9)0.1% -100.0~100.0 0.0 OH2.06 Current InputGain(Terminal 10)0.1% 0.0~200.0 100.0 OH2.07 Current InputBias(Terminal 10)0.1% -100.0~100.0 0.0 O• Adjust gain and bias of analog inputs, as shown in Figure 5.22 if thereare undesirable offset and gain changes in the analog inputs.• The setting unit of gain and bias changes according to the values inH2.05. For more details, see the paragraph 5.7.3.4.Figure 5.22 Gain and BiasAnalog inputMax. Output Frequency Gain100Max. Output Frequency Bias1000V(4mA) 10V(20mA)Use the current value in parenthesiswhen current input has been selectedWhen H2.05=0FrequencyCommand5-54 MOSCON-E7 User’s Manual5.7.3.4 Setting the multi-function analog input terminalfunction : H2.05ParameterNo. Name Unit Settingrange FactorySettingChangeableduringoperationH2.05 Function ofCurrentInput Terminal- 0~ 7 0• H2.05 is used to set the function of Ain(no. 10) terminal.• Constants and function for multi-function analog input• SettingSettingconstant Function Setting unit is the percentage of0 Frequency command Max. output frequency1 Frequency gain Max. output frequency2 Voltage bias Max. output voltage3 DC breaking current Max. output current4 Over torque detection level Max. output current5 Stall prevention level duringoperation Max. output current6 Minimum frequency commandlevel Max. output frequency7 Jump frequency Max. output frequency