1. Overview 1-9Starting Torque 150%/3HzMotor Overload Motor stops in 1 minute at approx. 150% ofmotor rated current.InstantaneousOvercurrent Motor stops immediately at 200% of inverterrated current.Inverter Overload Motor coasts to stop in 1 minute at approx.150% of inverter rated current.Overvoltage Motor stops at 410V or higher.Undervoltage Motor stops at 190V or lower.Cooling FinOverheat Motor stops if the temperature of the coolingfin is higher than approximately 90 .Momentary Power LossMotor stops if power loss is 15ms or longer,by selecting the momentary power loss mode,operation can be continued if power isrestored within 500ms.Stall Prevention Automatic setting during acceleration,deceleration, and constant speed operation(Individual setting is possible).Protective FunctionsPower ChargeIndication LED is ON until the DC bus voltage becomes50V or less.Location Indoor(Free from corrosive gas, dust, or oil)Ambient Temperature -10 ~ 40Humidity 90% RH or lessStorage Temperature -20 ~ 60 *3EnvironmentalconditionVibration Normally 0.2G or less, less than 20Hz, 1Gmax.*1. The maximum applicable motor capacity is for a standard 4-polemotor. When selecting the motor and inverter, make sure that theInverter’s rated current is applicable for the motor’s rated current.*2. Tuning may be required.*3. The storage temperature refers to the temperature during thetransportation for a short period of time.1-10 MOSCON-E7 User’s ManualTable 1.3 Specifications for 400V classSI-