[F145(SEND), H1607, WR3, H7788, K1](Note 1) Reads WR3 word data and sets it as write data.Command 15 (force multiple coils)● Example 3) Transfer from COM1 of 64 bits of data from WR3 0th bit to WR6 Fth bit to bitaddress H7788 of unit number 7[F145(SEND), H1507, WR3, H7788, K64][S1]:COM port selection Unit no. (H00 to HFF)H1 H5 H0 H7[S1]: H1507[S2]: WR3 (WR3=3210HWR4=7654HWR5=BA98HWR6=FEDCH)[D]: H7788[n]: K64Command conversionMODBUS commandSlave address 071Command (0FH) 0F2State change start number (H) 773State change start number (L) 884Change coil count (H) 005Change coil count (L) 406Data count (byte count) 087Set data 1 108Set data 2 329Set data 3 5410Set data 4 7611Set data 5 9812Set data 6 BA13Set data 7 DC14Set data 8 FE15CRC16(H) 3B16CRC16(L) 6517(Note 1) If multiple points are specified for n, the command will be corrected automatically.H5 bit single write => H15 bit multiple point write status change start number is H7788(destination unit)Change coil number will change write bit number to HEX. Change coil number maximum is 2040(07F8H) (due to MODBUS protocol limits)Data number (byte number) is calculated as 1 data (1 byte) for 8 coils. [Max 255 (FFH) bytes]8.1 Communication Instruction8-12 WUME-FP0HCOM-06