(Note 1) When sending command 15, set [S1] transfer method specification to word units (H0).(Note 2) Status change start number will be set to write target coil number. (destination unit)(Note 3) Change coil number will change write bit number to HEX.(Note 4) Due to MODBUS protocol limits, change coil number maximum is 2032 (07F0H).Data number (byte number) is calculated as 1 data (1 byte) for 8 coils. [Max 254 (FEH) bytes]Sending command 16 (DT multiple word write)● Example 4) Transfer from COM1 of 3 words of data from WR3 to WR5 to DT500–DT502 indestination unit number 7[F145(SEND), DT10, WR3, DT0, K500][S1]:Transfer inword unitsH0 H0 H0 H3Specifies the sendword count (H1 to H7F)DT10[S1]:COM port selectionH1 H0 H7[S1]: DT10 (DT10=0003H, DT11=1007H)[S2]: WR3 (WR3=0011HWR4=2233HWR5=4455H)[D]: DT0[n]: K500Command conversionMODBUS commandSlave address 071Command (10H) 102Write start number (H) 013Write start number (L) F44Write register count (H) 005Write register count (L) 036Data count (byte count) 067Write data 1 (H) 008Write data 1 (L) 119Write data 2 (H) 2210Write data 2 (L) 3311Write data 3 (H) 4412Write data 3 (L) 5513CRC16(H) 5A14CRC16(L) E715DT11H0 fixedUnit no. (H00 to H63)(0 to 99)(Note 1) When sending command 16 set [S1] transfer method specification to word units (H0).(Note 2) Due to MODBUS protocol limits, write resistor number maximum is 127 (7FH).(Note 3) Data number (byte number) is calculated as 2 bytes for write resistor number. [Max 254 (FEH)bytes]■ Flag operationsName DescriptionR9007R9008(ER)Turns ON when the [S1] / [S1+1] control data value is outside the specified range.Turns ON when the [S2] or [D] area is exceeded, if the number of words specified in [S1] istaken during transfer in word units.Turns ON when [D]+[n] exceeds the [D] area8.1 Communication InstructionWUME-FP0HCOM-06 8-23