76 en | Technical Data AMAX panel 2000 / AMAX panel 2000 ENF.01U.241.127 | V4 | 2011.12 Installation Manual Bosch Sicherheitssysteme GmbHAux (+12V/GND) Output: – Nominal Output Voltage under AC line input: 13,5 VDC +3%/ -5%– Output Voltage Range under AC line input: 12,82 VDC to13,9 VDC– 500mA maximum– Vpp (max) 675mVOption Bus: – Nominal Output Voltage under AC line input: 13,5 VDC +3%/ -5%– Output Voltage Range under AC line input: 12,82 VDC to13,9 VDC– 500mA maximumRF Power Output – 5VDC / 100mA maximumPanel PCB – Quiescent current maximum 100mABattery: – D126 (12V/7 Ah) sealed, lead acid rechargeable– Low battery condition is below 11,8 VDC– Minimum battery condition is 10,8VDC– Maximum auxiliary current to recharge standby battery to80% within 72h: 12 V/7 Ah Battery: 550mACertification: – EN 50131-3 GRADE 2 ENV-II = ENVIRONMENTAL GRADE IIKeypads:IUI-AMAX-LED8 (8Zone LED Keypad)Relative Humidity: – 10%-95%Operating Temperature: – -10°C - +55°CInput Voltage range: – 10VDC - 14VDCCurrent Consumption – standby 24mA– maximum 50mACable requirements: – four wire, unshielded and shielded 0,6-0,8mm– maximum length 150mEN type: – BIUI-AMAX-LCD8 (8Zone LCD Keypad)Relative Humidity: – 10%-95%Operating Temperature: – -10°C - +55°CInput Voltage range: – 10VDC - 14VDCCurrent Consumption – standby 18mA– maximum 60mACable requirements: – four wire, unshielded and shielded 0,6-0,8mm– maximum length 150mEN type: – B