56 en | System Informations 2 AMAX panel 2000 / AMAX panel 2000 ENF.01U.241.127 | V4 | 2011.12 Installation Manual Bosch Sicherheitssysteme GmbH8 System Informations 28.1 General overview on zones8.1.1 Zone InputsOn-board Inputs:There are 8 onboard hard-wired inputs for AMAX panel 2000 / AMAX panel 2000 EN. Anadditional input is provided for enclosure tamper but does not subtract from the 8 onboardtotals.On-board Zone Response Time:Each on-board zone response time is:Zone Status trigger time >= 400ms, must responseZone Status trigger time < 300ms, no responseOn board Zone EOL1. Single EOL: If 24-zone tamper function is not detected, each zone uses a single 2.2k ohmEOL. The panel can detect the zone as short, normal or open.The detectors(sensors) will be connected between zone and COM terminal through EOLseries connection (open triggered) or EOL parallel connection (short triggered).Figure 8.1 Open TriggeredFigure 8.2 Short TriggeredThe panel sets the short/open as activate when connecting with single EOL.The valid zone number is 1-8 for AMAX.2. Dual EOL: If the tamper supervision is set, we only can use the NC contact point. TheEOL status is :Loop Resistance (ohm) Zone StatusMin Typ Max1430 triggered1650 2200 2750 normal2970 triggeredLoop resistance (ohm) Zone StatusMin Type Max1430 tamperCOMZoneCOMZone