Direct Access Parameter InformationQ9 Plus ASD Install/Op Manualhttps://www.toshiba.com/tic/ 215ASD-to-ASD Communication (2-wire RS485)Program Communications Communication SettingsThe function of this parameter is two-fold:1) In a Master/Follower configuration and while communicatingvia RS4852-wire, this parameter sets the ASD as the Master or the Fol-lower.2) This parameter determines the function of the ASD while oper-ating as the Master or the Follower. If operating as the Mas-ter ASD, an output parameter of the Master ASD is used tocontrol the Follower ASDs and is set here.If operating as a Follower ASD, the ASD response if an error isincurred is set here.Note: Select a Follower function here if F826 is configured as aMaster Output controller for any other ASD in the system.Otherwise, an EOI failure will result.Changes made to this parameter require that the power becycled (off then on) for the changes to take effect.Settings:0 — Follower (Decel Stop If Error Detected)1 — Follower (Continues Operation If Error Detected)2 — Follower (Emergency Off If Error Detected)3 — Master (Frequency Command)4 — Master (Output Frequency)5 — Master (Torque Reference)6 — Master (Output Torque)Direct Access Number — F806Parameter Type — Selection ListFactory Default — Follower(Decel Stop)Changeable During Run — YesCommunication Protocol (2-Wire RS485)Program Communications Communication SettingsThis parameter sets the 2-Wire RS485 communicationsprotocol.Settings:0 — Toshiba1 — ModbusDirect Access Number — F807Parameter Type — Selection ListFactory Default — ToshibaChangeable During Run — NoCommunication 1 Time-Out ConditionProgram Communications Communication SettingsThis parameter determines the condition under which thedrive will detect time-out errors.Settings:0 — Always Detect1 — Detect Time-Out Error During Communications2 — Detect Time-Out Error During Communications andRunningDirect Access Number — F808Parameter Type — Selection ListFactory Default — Always DetectChangeable During Run — YesF806 – F810