Direct Access Parameter InformationQ9 Plus ASD Install/Op Manualhttps://www.toshiba.com/tic/ 127Jog FrequencyProgram Frequency Jog SettingsThis parameter sets the output frequency of the ASD during aJog. Jogging is the term used to describe turning on the motor forsmall increments of time and is used when precise positioning ofmotor-driven equipment is required.The Jog function is initiated via the Terminal Board or using Com-munications (see the Communications manual-P/N 53840 foradditional information on using Communications for Jogging).The Jog function can be activated from zero Hz or from any fre-quency below the Jog Run Frequency setting (Jog can onlyincrease the speed). A Jog command will not be recognizedwhen the running frequency is above the Jog Run Frequency set-ting. The Jog command has priority over other Run commandsand is not limited by the Upper-Limit setting of parameter F012.Jog commands received for the opposite direction of the com-manded frequency will follow the programmed stopping methodof F261 until reaching zero Hz and will then ramp to the pro-grammed Jog Frequency and direction.Jog Setup and ExecutionTo initiate a Jog Run from the EOI perform the following:7. Set the Command Mode Selection (F003) to EOI Keypad.This setting places the ASD in the Remote mode.8.Set the Frequency Mode Selection (F004) to EOI Keypad.9.Enable the Jog function (F262).10.Set the Input Terminal Priority (F106) function to Enable toreceive Jog commands.11.Assign the Jog Run setting to any unused discrete input ter-minal (Select from Table 9 on page 252).12.Set the Jog Frequency at F260.13.Set up a Jog Stop Pattern at F261.14.Press the Run key and the ASD will output the commandedfrequency (as programmed; not the Jog frequency).15.Activate the Jog Run terminal (from step 11). The ASD willoutput the Jog frequency setting of F260 (from step 12) for theduration of the activation.16.Stop the Jog by either providing a Stop command or termi-nating the Jog Run terminal activation. Providing a Stop com-mand will terminate the commanded frequency and the Jogfunction. Terminating the Jog Run terminal activation will ter-minate the Jog function only and will resume the commandedfrequency of step 14.Direct Access Number — F260Parameter Type — NumericalFactory Default — (ASD-Depen-dent)Changeable During Run — YesMinimum — Start Frequency(F240)Maximum — (ASD-Dependent)Units — HzF260 – F261