NCK alarms11/2006 Overview of Alarms2-97© Siemens AG, 2006. All rights reservedSINUMERIK, SIMODRIVE Diagnostics Manual (DA), 11/2006 Edition10203 Channel %1 NC start without reference point (action=%2)Parameters: %1 = Channel number%2 = Action number/action nameDefinitions: NC start has been activated in the MDI or AUTOMATIC mode and at least one axis that needs to bereferenced has not reached its reference point.Reaction: Interface signals are set.Alarm display.Remedy: Please inform the authorized personnel/service department. Via the channel-specific MD 20700:REFP_NC_START_LOCK (NC Start without reference point) you can decide whether the axis mustbe referenced before NC Start or not. The start of referencing can be enabled channel-specific or axis-specific.Channel-specific reference point approach: The rising edge of the interface signal "activatereferencing" (DB 21 - 28, DBX 1.0) starts an automatic sequence which starts the axes of the channelin the same sequence as specified in the axis-specific MD 34110 REFP_CYCLE_NR (axis sequencechannel-specific referencing). 0: The axis does not participate in channel-specific referencing, but itmust be referenced for NC Start, -1: The axis does not participate in channel-specific referencing, butit need not be referenced for NC Start, 1- 8: Starting sequence for the channel-specific referencing(simultaneous start at the same no.), 1 - 31: CPU typeAxis-specific referencing: Press the direction key that corresponds to the approach direction in theaxis-specific MD 34010 REFP_CAM_MDIR_IS_MINUS (reference point approach in minus direction).ProgramContinuation:Clear alarm with NC START or RESET key and continue the program.10204 [up to SW 3.x only] Channel %1 general errorParameters: %1 = Channel numberDefinitions: A general error has occurred in the channel.Reaction: Alarm display.Remedy: This message indicates an internal conflict with no further consequences.ProgramContinuation:Clear alarm with the Delete key or NC START.10205 [up to SW 3.x only] Channel %1 internal error in %2Parameters: %1 = Channel number%2 = StringDefinitions: An internal error has occurred in the channel.Reaction: Channel not ready.NC Start disable in this channel.Interface signals are set.Alarm display.NC Stop on alarm.Remedy: Press RESET.ProgramContinuation:Clear alarm with the RESET key. Restart part program10206 [up to SW 3.x only] Channel %1 general error in function generatorParameters: %1 = Channel numberDefinitions: An error has occurred during activation/deactivation of the function generator.Reaction: Alarm display.Remedy: Press RESET.ProgramContinuation:Clear alarm with the Delete key or NC START. PreviousNext |