3-36 N60 Network Stability and Synchrophasor Measurement System GE Multilin3.4 MANAGED ETHERNET SWITCH MODULES 3 HARDWARE33.4.3 MANAGED SWITCH LED INDICATORSThe 10/100Base-T and 100Base-FX ports have LED indicators to indicate the port status.The 10/100Base-T ports have three LEDs to indicate connection speed, duplex mode, and link activity. The 100Base-FXports have one LED to indicate linkup and activity.Figure 3–43: ETHERNET SWITCH LED INDICATORS3.4.4 CONFIGURING THE MANAGED ETHERNET SWITCH MODULEA suitable IP/gateway and subnet mask must be assigned to both the switch and the UR relay for correct operation. TheSwitch has been shipped with a default IP address of 192.168.1.2 and a subnet mask of 255.255.255.0. Consult your net-work administrator to determine if the default IP address, subnet mask or default gateway needs to be modified.Do not connect to network while configuring the switch module.a) CONFIGURING THE SWITCH MODULE IP SETTINGSIn our example configuration of both the Switch’s IP address and subnet mask must be changed to 3.94.247.229 and255.255.252.0 respectively. The IP address, subnet mask and default gateway can be configured using either EnerVistaUR Setup software, the Switch’s Secure Web Management (SWM), or through the console port using CLI.1. Select the Settings > Product Setup > Communications > Ethernet Switch > Configure IP menu item to open theEthernet switch configuration window.842868A2.CDRConnection speed indicator (OFF = 10 Mbps; ON = 100 Mbps)Link indicator (ON = link active; FLASHING = activity)Duplex mode indicator (OFF = half-duplex; ON = full-duplex)Link indicator (ON = link active; FLASHING = activity)CAUTION