GE Multilin N60 Network Stability and Synchrophasor Measurement System 5-1855 SETTINGS 5.8 TRANSDUCER INPUTS/OUTPUTS55.8.3 DCMA OUTPUTSPATH: SETTINGS ÖØ TRANSDUCER I/O ÖØ DCMA OUTPUTS Ö DCMA OUTPUT F1(W8)Table 5–13: RTD TEMPERATURE VS. RESISTANCETEMPERATURE RESISTANCE (IN OHMS)°C °F 100 W PT(DIN 43760)120 W NI 100 W NI 10 W CU–50 –58 80.31 86.17 71.81 7.10–40 –40 84.27 92.76 77.30 7.49–30 –22 88.22 99.41 82.84 7.88–20 –4 92.16 106.15 88.45 8.26–10 14 96.09 113.00 94.17 8.650 32 100.00 120.00 100.00 9.0410 50 103.90 127.17 105.97 9.4220 68 107.79 134.52 112.10 9.8130 86 111.67 142.06 118.38 10.1940 104 115.54 149.79 124.82 10.5850 122 119.39 157.74 131.45 10.9760 140 123.24 165.90 138.25 11.3570 158 127.07 174.25 145.20 11.7480 176 130.89 182.84 152.37 12.1290 194 134.70 191.64 159.70 12.51100 212 138.50 200.64 167.20 12.90110 230 142.29 209.85 174.87 13.28120 248 146.06 219.29 182.75 13.67130 266 149.82 228.96 190.80 14.06140 284 153.58 238.85 199.04 14.44150 302 157.32 248.95 207.45 14.83160 320 161.04 259.30 216.08 15.22170 338 164.76 269.91 224.92 15.61180 356 168.47 280.77 233.97 16.00190 374 172.46 291.96 243.30 16.39200 392 175.84 303.46 252.88 16.78210 410 179.51 315.31 262.76 17.17220 428 183.17 327.54 272.94 17.56230 446 186.82 340.14 283.45 17.95240 464 190.45 353.14 294.28 18.34250 482 194.08 366.53 305.44 18.73 DCMA OUTPUT F1DCMA OUTPUT F1SOURCE: OffRange: Off, any analog actual value parameterMESSAGE DCMA OUTPUT F1RANGE: –1 to 1 mARange: –1 to 1 mA, 0 to 1 mA, 4 to 20 mAMESSAGE DCMA OUTPUT F1MIN VAL: 0.000 puRange: –90.000 to 90.000 pu in steps of 0.001MESSAGE DCMA OUTPUT F1MAX VAL: 1.000 puRange: –90.000 to 90.000 pu in steps of 0.001