4-16 N60 Network Stability and Synchrophasor Measurement System GE Multilin4.3 FACEPLATE INTERFACE 4 HUMAN INTERFACES4Figure 4–19: LED PANELS 2 AND 3 (INDEX TEMPLATE)DEFAULT LABELS FOR LED PANEL 2:The default labels are intended to represent:• GROUP 1...6: The illuminated GROUP is the active settings group.• BREAKER 1(2) OPEN: The breaker is open.• BREAKER 1(2) CLOSED: The breaker is closed.• BREAKER 1(2) TROUBLE: A problem related to the breaker has been detected.• SYNCHROCHECK NO1(2) IN-SYNCH: Voltages have satisfied the synchrocheck element.The relay is shipped with the default label for the LED panel 2. The LEDs, however, are not pre-programmed. To match thepre-printed label, the LED settings must be entered as shown in the User-programmable LEDs section of chapter 5. TheLEDs are fully user-programmable. The default labels can be replaced by user-printed labels for both panels as explainedin the following section.Figure 4–20: LED PANEL 2 (DEFAULT LABELS)4.3.3 CUSTOM LABELING OF LEDSa) ENHANCED FACEPLATEThe following procedure requires the pre-requisites listed below.• EnerVista UR Setup software is installed and operational.• The N60 settings have been saved to a settings file.• The N60 front panel label cutout sheet (GE Multilin part number 1006-0047) has been downloaded from http://www.GEindustrial.com/multilin/support/ur and printed.• Small-bladed knife.This procedure describes how to create custom LED labels for the enhanced front panel display.1. Start the EnerVista UR Setup software.USER-PROGRAMMABLE LEDS USER-PROGRAMMABLE LEDS842782A1.CDR842785A1.CDR