E-8 N60 Network Stability and Synchrophasor Measurement System GE MultilinE.2 DNP POINT LISTS APPENDIX EEE.2DNP POINT LISTS E.2.1 BINARY INPUT POINTSThe DNP binary input data points are configured through the PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ DNP / IEC104 POINTLISTS Ö BINARY INPUT / MSP POINTS menu. Refer to the Communications section of Chapter 5 for additional details. When afreeze function is performed on a binary counter point, the frozen value is available in the corresponding frozen counterpoint.BINARY INPUT POINTSStatic (Steady-State) Object Number: 1Change Event Object Number: 2Request Function Codes supported: 1 (read), 22 (assign class)Static Variation reported when variation 0 requested: 2 (Binary Input with status), ConfigurableChange Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time), ConfigurableChange Event Scan Rate: 8 times per power system cycleChange Event Buffer Size: 500Default Class for All Points: 1