GE Multilin N60 Network Stability and Synchrophasor Measurement System 6-176 ACTUAL VALUES 6.3 METERING66.3.3 SENSITIVE DIRECTIONAL POWERPATH: ACTUAL VALUES ÖØ METERING ÖØ SENSITIVE DIRECTIONAL POWERThe effective operating quantities of the sensitive directional power elements are displayed here. The display may be usefulto calibrate the feature by compensating the angular errors of the CTs and VTs with the use of the RCA and CALIBRATIONsettings.6.3.4 SYNCHROCHECKPATH: ACTUAL VALUES ÖØ METERING ÖØ SYNCHROCHECK Ö SYNCHROCHECK 1(2)The actual values menu for synchrocheck 2 is identical to that of synchrocheck 1. If a synchrocheck function setting is "Dis-abled", the corresponding actual values menu item will not be displayed.6.3.5 TRACKING FREQUENCYPATH: ACTUAL VALUES ÖØ METERING ÖØ TRACKING FREQUENCYThe tracking frequency is displayed here. The frequency is tracked based on the selection of the reference source with theFREQUENCY AND PHASE REFERENCE setting in the SETTINGS ÖØ SYSTEM SETUP ÖØ POWER SYSTEM menu. Refer to thePower System section of chapter 5 for additional details.6.3.6 FLEXELEMENTS™PATH: ACTUAL VALUES ÖØ METERING ÖØ FLEXELEMENTS Ö FLEXELEMENT 1(16)The operating signals for the FlexElements™ are displayed in pu values using the following definitions of the base units. SENSITIVE DIRECTIONAL POWERDIRECTIONAL POWER 13Φ: 0.000 WMESSAGE DIRECTIONAL POWER 23Φ: 0.000 W SYNCHROCHECK 1SYNCHROCHECK 1 DELTAVOLT: 0.000 VMESSAGE SYNCHROCHECK 1 DELTAPHASE: 0.0°MESSAGE SYNCHROCHECK 1 DELTAFREQ: 0.00 Hz TRACKING FREQUENCYTRACKING FREQUENCY:60.00 Hz FLEXELEMENT 1FLEXELEMENT 1OpSig: 0.000 puTable 6–2: FLEXELEMENT™ BASE UNITS (Sheet 1 of 2)dcmA BASE = maximum value of the DCMA INPUT MAX setting for the two transducers configuredunder the +IN and –IN inputs.FREQUENCY f BASE = 1 HzPHASE ANGLE ϕBASE = 360 degrees (see the UR angle referencing convention)POWER FACTOR PF BASE = 1.00RTDs BASE = 100°CSENSITIVE DIR POWER(Sns Dir Power)PBASE = maximum value of 3 × V BASE × IBASE for the +IN and –IN inputs of the sourcesconfigured for the sensitive power directional element(s).