3-30 N60 Network Stability and Synchrophasor Measurement System GE Multilin3.3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE33.3.5 RS422 INTERFACEa) DESCRIPTIONThere are three RS422 inter-relay communications modules available: single-channel RS422 (module 7T), dual-channelRS422 (module 7W), and dual-channel dual-clock RS422 (module 7V). The modules can be configured to run at 64 or128 kbps. AWG 24 twisted shielded pair cable is recommended for external connections. These modules are protected byoptically-isolated surge suppression devices.The two-channel two-clock RS422 interface (module 7V) is intended for use with two independent channel bankswith two independent clocks.The shield pins (6a and 7b) are internally connected to the ground pin (8a). Proper shield termination is as follows:• Site 1: Terminate shield to pins 6a or 7b or both.• Site 2: Terminate shield to COM pin 2b.The clock terminating impedance should match the impedance of the line.Figure 3–35: RS422 INTERFACE CONNECTIONSThe following figure shows the typical pin interconnection between two single-channel RS422 interfaces installed in slot W.All pin interconnections are to be maintained for a connection to a multiplexer.Figure 3–36: TYPICAL PIN INTERCONNECTION BETWEEN TWO RS422 INTERFACESb) TWO-CHANNEL APPLICATION VIA MULTIPLEXERSThe RS422 interface may be used for single channel or two channel applications over SONET/SDH or multiplexed sys-tems. When used in single-channel applications, the RS422 interface links to higher order systems in a typical fashionobserving transmit (Tx), receive (Rx), and send timing (ST) connections. However, when used in two-channel applications,certain criteria must be followed since there is one clock input for the two RS422 channels. The system will function cor-rectly if the following connections are observed and your data module has a terminal timing feature. Terminal timing is acommon feature to most synchronous data units that allows the module to accept timing from an external source. Using theterminal timing feature, two channel applications can be achieved if these connections are followed: The send timing out-puts from the multiplexer (data module 1), will connect to the clock inputs of the UR–RS422 interface in the usual fashion.In addition, the send timing outputs of data module 1 will also be paralleled to the terminal timing inputs of data module 2.NOTE~~~~~~~~~~~~~~ShieldShieldCOMTx +Tx +Tx –Tx –Rx –Rx –Rx +Rx +3b5b2a4a6a7b8b ClockRS422channel 1RS422channel 2Surge3a5a4b6b7a2b8aInter-relay communications 7W842776A3.CDRDual-channel RS422 module~~~~~ShieldTx +Tx –Rx –Rx +3b2a6aRS4223a4b~~~~COM8b ClockSurge7a2b8aInter-relay comms. 7TSingle-channel RS422 module~ indicates the slot position