6-24 G60 Generator Protection System GE Multilin6.3 METERING 6 ACTUAL VALUES66.3.9 IEC 61580 GOOSE ANALOG VALUESPATH: ACTUAL VALUES METERING IEC 61850 GOOSE ANALOGSThe G60 Generator Protection System is provided with optional IEC 61850 communications capability.This feature is specified as a software option at the time of ordering. Refer to the Ordering section of chap-ter 2 for additional details.The IEC 61850 GGIO3 analog input data points are displayed in this menu. The GGIO3 analog data values are receivedvia IEC 61850 GOOSE messages sent from other devices.6.3.10 SENSITIVE DIRECTIONAL POWERPATH: ACTUAL VALUES METERING SENSITIVE DIRECTIONAL POWERThe effective operating quantities of the sensitive directional power elements are displayed here. The display may be usefulto calibrate the feature by compensating the angular errors of the CTs and VTs with the use of the RCA and CALIBRATIONsettings.6.3.11 STATOR GROUNDPATH: ACTUAL VALUES METERING STATOR GROUNDMagnitudes of the third harmonic components of the machine neutral point voltage (VN), the zero-sequence voltage at themachine terminals (V0), and in the vector sum of the neutral point voltage and zero-sequence voltage (VN + V0) are avail-able for display. The values are calculated for a signal source specified under the stator ground settings menu.These readings may be useful when selecting a pickup and supervision setting for the 100% stator ground and third har-monic neutral undervoltage protection elements. IEC 61850 GOOSE ANALOGSANALOG INPUT 10.000MESSAGE ANALOG INPUT 20.000MESSAGE ANALOG INPUT 30.000↓MESSAGE ANALOG INPUT 320.000 SENSITIVE DIRECTIONAL POWERDIRECTIONAL POWER 13Φ: 0.000 WMESSAGE DIRECTIONAL POWER 23Φ: 0.000 W STATOR GROUNDSTATOR GND 3RD HARMVN: 0.000 VMESSAGE STATOR GND 3RD HARMVN+V0: 0.000 VMESSAGE STATOR GND 3RD HARMV0: 0.000 V