GE Multilin G60 Generator Protection System 5-3015 SETTINGS 5.8 INPUTS/OUTPUTS5Remote outputs (1 to 32) are FlexLogic operands inserted into GSSE/GOOSE messages that are transmitted to remotedevices on a LAN. Each digital point in the message must be programmed to carry the state of a specific FlexLogic oper-and. The above operand setting represents a specific DNA function (as shown in the following table) to be transmitted.b) USERST BIT PAIRSPATH: SETTINGS INPUTS/OUTPUTS REMOTE OUTPUTS UserSt BIT PAIRS REMOTE OUTPUTS UserSt- 1(32) BIT PAIRRemote outputs 1 to 32 originate as GSSE/GOOSE messages to be transmitted to remote devices. Each digital point in themessage must be programmed to carry the state of a specific FlexLogic operand. The setting above is used to select theoperand which represents a specific UserSt function (as selected by the user) to be transmitted.For more information on GSSE/GOOSE messaging, refer to Remote Inputs/Outputs Overview in the RemoteDevices section.5.8.9 RESETTINGPATH: SETTINGS INPUTS/OUTPUTS RESETTINGSome events can be programmed to latch the faceplate LED event indicators and the target message on the display. Onceset, the latching mechanism will hold all of the latched indicators or messages in the set state after the initiating conditionhas cleared until a RESET command is received to return these latches (not including FlexLogic latches) to the reset state.The RESET command can be sent from the faceplate Reset button, a remote device via a communications channel, or anyprogrammed operand.When the RESET command is received by the relay, two FlexLogic operands are created. These operands, which arestored as events, reset the latches if the initiating condition has cleared. The three sources of RESET commands each cre-ate the RESET OP FlexLogic operand. Each individual source of a RESET command also creates its individual operandRESET OP (PUSHBUTTON), RESET OP (COMMS) or RESET OP (OPERAND) to identify the source of the command. The settingshown above selects the operand that will create the RESET OP (OPERAND) operand.Table 5–34: IEC 61850 DNA ASSIGNMENTSDNA IEC 61850 DEFINITION FLEXLOGIC OPERAND1 Test IEC 61850 TEST MODE2 ConfRev IEC 61850 CONF REV REMOTE OUTPUTS UserSt- 1 BIT PAIRUserSt- 1 OPERAND:OffRange: FlexLogic operandMESSAGE UserSt- 1 EVENTS:DisabledRange: Disabled, Enabled RESETTINGRESET OPERAND:OffRange: FlexLogic operandNOTE