5-214 G60 Generator Protection System GE Multilin5.6 GROUPED ELEMENTS 5 SETTINGS55.6.12 BREAKER FAILUREPATH: SETTINGS GROUPED ELEMENTS SETTING GROUP 1(6) BREAKER FAILURE BREAKER FAILURE 1(4) BREAKER FAILURE 1BF1 FUNCTION:DisabledRange: Disabled, EnabledMESSAGE BF1 MODE:3-PoleRange: 3-Pole, 1-PoleMESSAGE BF1 SOURCE:SRC 1Range: SRC 1, SRC 2, SRC 3, SRC 4MESSAGE BF1 USE AMP SUPV:YesRange: Yes, NoMESSAGE BF1 USE SEAL-IN:YesRange: Yes, NoMESSAGE BF1 3-POLE INITIATE:OffRange: FlexLogic operandMESSAGE BF1 BLOCK:OffRange: FlexLogic operandMESSAGE BF1 PH AMP SUPVPICKUP: 1.050 puRange: 0.001 to 30.000 pu in steps of 0.001MESSAGE BF1 N AMP SUPVPICKUP: 1.050 puRange: 0.001 to 30.000 pu in steps of 0.001MESSAGE BF1 USE TIMER 1:YesRange: Yes, NoMESSAGE BF1 TIMER 1 PICKUPDELAY: 0.000 sRange: 0.000 to 65.535 s in steps of 0.001MESSAGE BF1 USE TIMER 2:YesRange: Yes, NoMESSAGE BF1 TIMER 2 PICKUPDELAY: 0.000 sRange: 0.000 to 65.535 s in steps of 0.001MESSAGE BF1 USE TIMER 3:YesRange: Yes, NoMESSAGE BF1 TIMER 3 PICKUPDELAY: 0.000 sRange: 0.000 to 65.535 s in steps of 0.001MESSAGE BF1 BKR POS1 φA/3P:OffRange: FlexLogic operandMESSAGE BF1 BKR POS2 φA/3P:OffRange: FlexLogic operandMESSAGE BF1 BREAKER TEST ON:OffRange: FlexLogic operandMESSAGE BF1 PH AMP HISETPICKUP: 1.050 puRange: 0.001 to 30.000 pu in steps of 0.001MESSAGE BF1 N AMP HISETPICKUP: 1.050 puRange: 0.001 to 30.000 pu in steps of 0.001MESSAGE BF1 PH AMP LOSETPICKUP: 1.050 puRange: 0.001 to 30.000 pu in steps of 0.001