5-74 G60 Generator Protection System GE Multilin5.2 PRODUCT SETUP 5 SETTINGS55.2.13 USER-PROGRAMMABLE PUSHBUTTONSPATH: SETTINGS PRODUCT SETUP USER-PROGRAMMABLE PUSHBUTTONS USER PUSHBUTTON 1(16)The optional user-programmable pushbuttons (specified in the order code) provide an easy and error-free method of enter-ing digital state (on, off) information. The number of available pushbuttons is dependent on the faceplate module orderedwith the relay.• Type P faceplate: standard horizontal faceplate with 12 user-programmable pushbuttons.• Type Q faceplate: enhanced horizontal faceplate with 16 user-programmable pushbuttons.The digital state can be entered locally (by directly pressing the front panel pushbutton) or remotely (via FlexLogic oper-ands) into FlexLogic equations, protection elements, and control elements. Typical applications include breaker control,autorecloser blocking, and setting groups changes. The user-programmable pushbuttons are under the control level ofpassword protection.The user-configurable pushbuttons for the enhanced faceplate are shown below. USER PUSHBUTTON 1PUSHBUTTON 1FUNCTION: DisabledRange: Self-Reset, Latched, DisabledMESSAGE PUSHBTN 1 ID TEXT: Range: Up to 20 alphanumeric charactersMESSAGE PUSHBTN 1 ON TEXT: Range: Up to 20 alphanumeric charactersMESSAGE PUSHBTN 1 OFF TEXT: Range: Up to 20 alphanumeric charactersMESSAGE PUSHBTN 1 HOLD:0.0 sRange: 0.0 to 10.0 s in steps of 0.1MESSAGE PUSHBTN 1 SET:OffRange: FlexLogic operandMESSAGE PUSHBTN 1 RESET:OffRange: FlexLogic operandMESSAGE PUSHBTN 1 AUTORST:DisabledRange: Disabled, EnabledMESSAGE PUSHBTN 1 AUTORSTDELAY: 1.0 sRange: 0.2 to 600.0 s in steps of 0.1MESSAGE PUSHBTN 1 REMOTE:OffRange: FlexLogic operandMESSAGE PUSHBTN 1 LOCAL:OffRange: FlexLogic operandMESSAGE PUSHBTN 1 DROP-OUTTIME: 0.00 sRange: 0 to 60.00 s in steps of 0.05MESSAGE PUSHBTN 1 LED CTL:OffRange: FlexLogic operandMESSAGE PUSHBTN 1 MESSAGE:DisabledRange: Disabled, Normal, High PriorityMESSAGE PUSHBUTTON 1EVENTS: DisabledRange: Disabled, Enabled