GE Multilin G60 Generator Protection System 5-995 SETTINGS 5.4 SYSTEM SETUP55.4.4 BREAKERSPATH: SETTINGS SYSTEM SETUP BREAKERS BREAKER 1(4) BREAKER 1BREAKER 1FUNCTION: DisabledRange: Disabled, EnabledMESSAGE BREAKER1 PUSH BUTTONCONTROL: DisabledRange: Disabled, EnabledMESSAGE BREAKER 1 NAME:Bkr 1Range: up to 6 alphanumeric charactersMESSAGE BREAKER 1 MODE:3-PoleRange: 3-Pole, 1-PoleMESSAGE BREAKER 1 OPEN:OffRange: FlexLogic operandMESSAGE BREAKER 1 BLK OPEN:OffRange: FlexLogic operandMESSAGE BREAKER 1 CLOSE:OffRange: FlexLogic operandMESSAGE BREAKER 1 BLK CLOSE:OffRange: FlexLogic operandMESSAGE BREAKER 1 ΦA/3P CLSD:OffRange: FlexLogic operandMESSAGE BREAKER 1 ΦA/3P OPND:OffRange: FlexLogic operandMESSAGE BREAKER 1 ΦB CLOSED:OffRange: FlexLogic operandMESSAGE BREAKER 1 ΦB OPENED:OffRange: FlexLogic operandMESSAGE BREAKER 1 ΦC CLOSED:OffRange: FlexLogic operandMESSAGE BREAKER 1 ΦC OPENED:OffRange: FlexLogic operandMESSAGE BREAKER 1 Toperate:0.070 sRange: 0.000 to 65.535 s in steps of 0.001MESSAGE BREAKER 1 EXT ALARM:OffRange: FlexLogic operandMESSAGE BREAKER 1 ALARMDELAY: 0.000 sRange: 0.000 to 65.535 s in steps of 0.001MESSAGE MANUAL CLOSE RECAL1TIME: 0.000 sRange: 0.000 to 65.535 s in steps of 0.001MESSAGE BREAKER 1 OUT OF SV:OffRange: FlexLogic operandMESSAGE BREAKER 1 EVENTS:DisabledRange: Disabled, Enabled