30Field setting modeEnglishField Setting ModeField Setting Value (FSV) 30**Code 30** : User’s options for Domestic Hot Water(DHW) tank heating࡙ The values in the following table are just examples for your understanding.Main Menu &Code Menu Function SubCodeMODEL CODE :AE200(260)RNW***MODEL CODE :MIM-E03CN /MIM-E03ENSetting Standard Setting StandardItem Step Unit Default Min. Max. Default Min. Max.DomesticHot WaterTankCode 30**DHWDHW modeactivate DHW mode - - 3011 1 0 2 0 0 2Heat PumpMax. Temp. 1 ઑA 3021 55 45 55 55 45 55Stop 1 ઑA 3022 0 0 10 2 0 10Start 1 ઑA 3023 5 5 30 5 5 30Min. OperatingTime 1 min 3024 5 1 20 5 1 20Max. OperatingTime 5 min 3025 30 5 95 30 5 95OperationInterval 0.5 hour 3026 3 0.5 10 3 0.5 10BoosterHeaterOn/Off - - 3031 1 (On) 0 (Off) 1 1 (On) 0 (Off) 1Delay Time 5 min 3032 20 20 95 20 20 95Overshoot 1 ઑA 3033 0 0 4 0 0 4DisinfectionOn/Off - - 3041 1 (On) 0 (Off) 1 1 (On) 0 (Off) 1Interval 1 day 3042 Fri (5) Sun (0) All (7) Fri (5) Sun (0) All (7)Start Time 1 o'clock 3043 23 0 23 23 0 23Target Temp. 5 ઑA 3044 70 40 70 70 40 70Duration 5 min 3045 10 5 60 10 5 60Max time 1 hour 3046 ߩ 1 24 ߩ 1 24Forced DHWOperationTimer OFFFunction - - 3051 0 (No) 0 1 (Yes) 0 (No) 0 1 (Yes)Time Duration 1 (x10)min 3052 6 3 30 6 3 30Solar Panel/DHWThermostatH/PCombination 1 - 3061 0 (No) 0 2 0 (No) 0 23-way Valve Defalut Direction - - 3071 0 (Room) 0 1 (Tank) 0 (Room) 0 1 (Tank)