29EnglishField Setting Mode࡙ When the remote controller is used, floor valve should be connected to zone #1 and the FCU valve shouldbe separately connected to zone #2 of the Hydro Unit PBA.࡙ When only floor cooling/heating is installed and if the Water Law or outlet water temperature is too low,2way valve may closed and E911 error may occur.࡙ When the floor and FCU units are installed together and operating in cooling mode, floor valve may closeand E911 may occur to prevent floor condensation when the outlet water temperature is below 16°C.Therefore FCU should secure minimum value for the flow rate.࡙ Thermostat #2 which controls FCU has the priority for operation modes and the discharge watertemperature.࡙ Samsung is not responsible for the accidents such as floor condensations which can occur by notconnecting the valve to the zone #1 port of the Hydro Unit PBA.Remote controller room temperature control࡙ Control by room temperature sensor (Service mode) ࣕIf set to #2093 1, the compressor can be turned on or off only by Room temp sensor. ࣕIf set to #2093 2~4, the compressor can be turned on or off by Room Temp. sensor or according to theWL discharged water temperature. ࣍ߤߪߡߣࢄࡡߣǮøƟ˵ʪθ͔ͱͱ˙˙२ǮɇϩʪθΧЇ͔Χͱ˙˙ࡡߤߪߡߣࢄࡡߤǮøƟ˵ʪθ͔ͱͱ˙ ˙२ǮɇϩʪθΧЇ͔Χͱ͝ࡡߤߪߡߣࢄࡡߥǮøƟ˵ʪθ͔ͱͱ˙˙२ǮɇϩʪθΧЇ͔Χߨ͔̈͝ͱ˙˙२ߤ͔̈͝ͱ͝२ࢋࢋࢋࢋࢋࢋࢋ࣎ࢋ