Panasonic Eco Solutions Nordic ABMEW01622 Rev: - EBL128 Planning Instructions V2.0.x7210 Output programmingOutput programming is done via EBLWin. See the EBLWin dialogbox respectively.10.1 TypeThe following output types are available (see also comments below):0. Control1. Fire Ventilation2. Extinguishing3. Alarm Device4. Routing Equipment (Fire brigade tx)5. Control, neutral6. Interlocking OutputComments to the types:0. Default. General (normal) control output701. Used to activate fire ventilation equipment712. Used to activate extinguishing equipment723. Used for sounders, etc.734. Used for fire alarm tx745. General (normal) control output. No collective disablement andno LED indication.6. Output used together with a corresponding interlocking input.See chapter "Interlocking function", page 88. Activated outputsare shown in menu H9/C1.70 Collectively disabled via menu H2/B4 (all control outputs). Re-enabledvia menu H2/B8.71 Collectively disabled via menu H2/B4 (all ventilation outputs). Re-enabled via menu H2/B8. LED "Ventilation" is indicating activated output.72 Collectively disabled via menu H2/B4 (all extinguishing outputs). Re-enabled via menu H2/B8. LED "Extinguishing" is indicating activatedoutput.73 Collectively disabled / re-enabled via menu H2/B9 (all alarm deviceoutputs). Controlled by push button "Silence alarm devices". Fault on /disabled output is indicated by LED "Fault / Disablements Alarm devices"blinking (fault) / continuous (disablement).74 Disabled / re-enabled via menu H2/B10 (Fire and/or fault outputs).Controlled via open door (if programmed so). Used together with triggercondition Fire brigade tx. LED "Fire brigade tx" is indicating activatedoutput. (Fire brigade tx feedback via a programmable input can light up theLED instead). Fault on / disabled output is indicated by LED "Fault /Disablements Fire brigade tx" blinking (fault) / continuous (disablement).