Panasonic Eco Solutions Nordic ABMEW01622 Rev: - EBL128 Planning Instructions V2.0.x648 Input programmingInput programming is done via EBLWin. Each input has to have anindividual Trigger condition ("Type") and Logic. Each input can besupervised or not supervised.8.1 Type (trigger conditions)The following trigger conditions are available (numbers only for theparagraph "Comments to the trigger conditions"):1. Activate output2. Activated fault routing equipment (one input)3. Activated fire ventilation (one input)4. Activated key cabinet (one input)5. Activated Routing Equipment (one input)6. Alarm Key Cabinet (one input)7. Alert Annunciation Acknowledge8. Alert Annunciation Reset9. Door Closing Test Input10. Evacuate (one input)11. External Fault (up to 50)12. External Time Channel (one input per time channel)13. Extinguishing alarm14. Extinguishing start15. Extinguishing stop16. Extinguishing system fault (one input)17. Extinguishing system released (one input)18. Fault Signal External Fuses (one input)19. Fault Signal External Power Supply (one input)20. Fault warning routing equipment fault (one input)21. General Fire (max. 100)22. Interlocking (max. 100)23. Loss of battery charger to external power supply (one input)24. Loss of main power source to external power supply (oneinput)25. Not used26. NZ Silence switch (one input)27. Pre-warning28. Technical warning (up to 50)29. Zone Line Input 64Comments to the trigger conditions:64 Only valid for the Addressable multipurpose I/O unit 3361 input "In0",used as zone line input (Z).