ENElectrical connectionKACO Operating Instructions blueplanet 15.0-20.0 TL3 Page 19Authorised electrician7.3 Preparing the DC connection7.3.1 Configuring the DC plug connector431 215512643 7Figure 15: Insert wires Figure 16: Slide insert into sleeve Figure 17: Check fasteningKey1 Wire for DC connection 5 Cable fitting2 Spring 6 Contact plug3 Insert 7 Coupling4 SleeveConfiguring the DC plug connectorNOTE: Before proceeding with the isolation ensure that you do not cut any individual wires.1. Isolate wire for DC connection by 15 mm.2. Insert isolated wire with twisted ends carefully up to the end stop.NOTE: Wire ends must be visible in the spring.3. Close the spring so that the spring latches.4. Slide insert into sleeve.5. Tighten cable fitting with the help of a 15 mm fork wrench applying a torque of 2 Nm.6. Join insert with contact plug.7. Check latch by lightly pulling on the coupling.» Make the electrical connection.NOTEThe permissible bending radius of at least 4x the cable diameter should be observed during installa-tion. Excessive bending force may negatively impact the protection rating.› All mechanical loads must be absorbed in front of the plug connection.› Rigid adaptations are not permitted on DC plug connectors.7.3.2 Checking the PV generator for a ground faultDANGERRisk of fatal injury due to electric shock!Severe injury or death will result if the live connections are touched. When there is solar radiation, DCvoltage will be present at the open ends of the DC cables.› Only touch the PV generator cables on the insulation. Do not touch the exposed ends of the cables.› Avoid short circuits.› Do not connect any strings with a ground fault to the unit.