ENENElectrical connectionPage 18 KACO Operating Instructions blueplanet 15.0-20.0 TL3Authorised electricianNOTESelect the following specifications in accordance with the following master conditions:- Country specific installation standards- Line length- Type of line installation- Local temperatures7.2 Connection to the power gridThe power connection wires are connected on the right of the connection area (see Figure 13 on page 17),DANGERRisk of fatal injury due to electric shock!Severe injury or death will result if the live connections are touched.› Switch off all power sources to the inverter before you insert the grid power cable into the unit.› Make sure that the device is isolated from the public power supply and the system power supplybefore starting work.NOTEIf the cable impedance is high (i.e. long grid-side cables), the voltage at the grid terminals of theinverter will increase during feed-in to the grid. The inverter monitors this voltage. If it exceeds thecountry-specific grid overvoltage limit value, the inverter switches off.› Ensure that the cable cross-sections are sufficiently large or that the cable lengths are sufficientlyshort.Connect the power supply Use cables with 5 wires (L1, L2, L3, N, PE).1. Unscrew the cable fitting.2. Remove the outer cladding of the AC cables.3. Insert the AC cables through the cable fitting into the connection area.4. Strip the insulation from the AC cables.5. Open the locks for the PCB terminals.6. Connect the cables in accordance with the label on the PCB terminals(Figure 14 on page 18).7. Close the locks for the PCB terminals.8. Check secure fit of all connected cables.9. Tighten the cable fitting.» The inverter is now connected to the power grid.PE NBUL2BKL1BNGNYEL3GYFigure 14: AC connection terminalsNOTEAn AC-side disconnection unit must be provided during the final installation stage. This cut-offmechanism must be installed so that it can be accessed at any time without obstruction.NOTEIf a residual current circuit breaker is necessary due to the installation specification, a type A residualcurrent circuit breaker must be used.If the type A is used, the insulation threshold must be set to greater than/equal to (≥) 200kOhm inthe “Parameters” menu (section 8.3 on Page 39).For questions regarding the appropriate type, please contact your installer or our KACO new energycustomer service.