Section 3 – Installing the Control3-23Connecting the Card ReaderLead from Reader Lead Color To VistaKey TB3 Terminal #Green LED Orange 1Ground* Black 2DATA 1 (Clock) White 3DATA 0 (Data) Green 4+5VDC† Red† 6+12VDC† Red† 7* TB-3 Terminal 5 is also a ground and may be used instead of terminal 2. Terminals 2 and 5 are a common ground.† Connect to +5VDC OR +12VDC per reader manufacturer’s specification.+WEEKLY TESTING IS REQUIREDTO ENSURE PROPER OPERATIONOF THIS SYSTEM.POLE Door Strike/Mag CoilDATA 1 (WHITE)DATA 0 (GREEN)NOTE 1: USE UL LISTED ENERGY CABLE FOR ALL CONNECTIONS.NOTE 2: VISTAKEY TB3 TERMINAL 5 IS A GROUND AND MAY BEUSED INSTEAD OF TB3 TERMINAL 2. TB3 TERMINALS 2 AND 5 AREA COMMON GROUND.NOTE 3: WHEN USING TRIGGER TO TURN ON AN LED OR BUZZER,RETURN HIGH SIDE OF LED OR BUZZER TO TB3 TERMINAL 7.TRIGGER RATING IS 15mA AT 12VDC.+5VGNDTRIGGER (SEE NOTE 3)+12V (RED)ZONE C (General)ZONE A (DSM)ZONE B (RTE)POLLING LOOP -14V MAX (12V @ 85-160mA Nominal)POLLING LOOP +GNDGNDGNDN/O DOOR STRIKE POWERN/C MAG COIL POWER234567811 122 3 4 5 6 7 8 9 101 RELAY CONTACT RATINGS:3A @ 28VDC MAX. (RESISTIVE LOAD)TB 1TB 31READER INTERFACE CABLEGND (BLACK)RDR LED (ORANGE)TO ALARM SYSTEMCONTROL PANELPOLLING LOOP TERMINALS.NOCONNECTIONVISTAKEYTHIS DEVICE COMPLIES WITH PART 15 CLASS ALIMITS OF FCC RULES. OPERATION IS SUBJECTTO THE FOLLOWING TWO CONDITIONS:(1) IT MAY NOT CAUSE HARMFUL INTERFERENCE.(2) IT MUST ACCEPT ANY INTERFERENCE THATMAY CAUSE UNDESIRED OPERATION.K1DOORCONTROLRELAYFOR ADDITIONAL RATINGS ANDSPECIFICATIONS, REFER TOINSTALLATION INSTRUCTIONFOR THE VISTAKEY-SK.THIS EQUIPMENT SHOULD BE INSTALLED INACCORDANCE WITH THE NATIONAL FIREPROTECTION ASSOCIATION'S STANDARDS 70 &74 (NATIONAL FIRE PROTECTION ASSOC.,BATTERYMARCH PARK, QUINCY, MA. 02269).PRINTED INFORMATION DESCRIBING PROPERMAINTENANCE, EVACUATION PLANNING ANDREPAIR SERVICE IS TO BE PROVIDED WITHTHIS EQUIPMENT.TO TB1, 11 OR 12+ 12 VDC TO ONLYONE OF THESE INPUTS.(FROM TB1-1)Figure 3-22: Wiring the VistaKey