Excel 800 LIONEN1B-0375GE51 R0308 66CLIOL823A Binary Input ModuleOne instance of the LONMARK open-loop sensor object hasbeen assigned per input of the CLIOL823A Binary InputModule.Each digital input object has its own configurationproperties, except for heartbeat configuration, which will beshared among all objects.nvoDiSwitch[x]SNVT_switchnvoDiCount[x]SNVT_countConfigurationParameterValue FileOpen Loop Sensor Object(LonMark Object Type 1)|1#1nciDiConfig[x]UCPT_DIConfignciSndHrtBtSCPTmaxSendTimeFig. 93 LONMARK digital input objectTransmissionThese variables are transmitted immediately when its valuehas been changed by a higher rate than the configured"send on delta" (in the case of the totalizer, “send on delta”has a default value of 5 counts).These variables are also transmitted as a heartbeat outputon a regular basis as dictated by the maximum send time(nciSndHrtBt) (default = 0 = disabled) configuration variable.Default Service TypeThe default service type of these variables isunacknowledged.Fast Binary Input – nvoDiSwitch[ ]This network variable output represents the logical state of afast binary input connected to the binary input terminals.Valid RangeLogical input state Value StateON 100 % 1OFF 0 % 0Not configured 0 % -1Table 65 Slow digital input valuesDefault ValueThe default value is set after power-up or reset and remainsuntil the module has measured a valid value.Value = 0State = -1Totalizer Count – nvoDiCount[ ]This network variable output indicates the total number oftransitions from 0 to 1 since the last reset due to power-upor network reset.Valid RangeFig. 94 TotalizerState ValueFor totalizer counts 0 … 65534For power-up/reset 65535Table 66 Totalizer countsPower-up/ResetAfter power-up and reset, the value 0xFFFF = 65535 will besent to the network to indicate that previous count valueshave been lost due to a reset.