Excel 800 LIONEN1B-0375GE51 R0308 4Safety InformationGeneral Safety Information► When performing any work (installation, mounting, start-up), all instructions given by the manufacturer and inparticular the safety instructions provided in theseInstallation and Commissioning Instructions are to beobserved.► The Excel 800 LION System (including the CLLIONLC01Controller Module, I/O modules, manual disconnectmodules, and the auxiliary terminal package) may beinstalled and mounted only by authorized and trainedpersonnel.► Rules regarding electrostatic discharge should befollowed.► If the Excel 800 LION System is modified in any way,except by the manufacturer, all warranties concerningoperation and safety are invalidated.► Make sure that the local standards and regulations areobserved at all times. Examples of such regulations areVDE 0800 and VDE 0100 or EN 60204-1 for earthgrounding.► Use only accessory equipment which comes from or hasbeen approved by Honeywell.► It is recommended that devices are to be kept at roomtemperature for at least 24 hours before applying power.This is to allow any condensation resulting from lowshipping/storage temperatures to evaporate.► The Excel 800 LION System must be installed in such amanner (e.g., in a lockable cabinet) as to ensure thatuncertified persons have no access to the terminals.Safety Information as perEN60730-1:2005-12PurposeThe Excel 800 LION System is an independently mountedelectronic control system with fixed wiring.It is used for the purpose of building HVAC control and issuitable for use only in non-safety controls for installation onor in appliances.Pollution degree Pollution Degree 2,suitable for use in residentialcontrols, commercial controls,in a clean environment.OvervoltagecategoryCategory IIfor mains-powered (16A) controlsCategory Ifor 24 V powered controlsRated impulsevoltage2500 VACAutomatic action Type 1.C(micro-interruption for the relayoutputs)Software class Class ABall-pressure testtemperature75 °C for all housing and plasticparts125 °C in the case of devicesapplied with voltage-carrying partsand connectorsElectromagneticinterferenceTested at 230 VAC,with the modules in normalcondition.System transformer Europe: safety isolatingtransformers according toIEC61558-2-6U.S.A. and Canada: NEC Class-2transformersTable 1 System data as per EN60730-1:2005-12