Excel 800 LIONEN1B-0375GE51 R0308 58TerminalsActuator 2 Actuator 331 41 51 6132 42 52 6233 43 53 6334 44 54 64NONCCOMCONNONCCOMCON1112131421222324 25NONCCOMCONNONCCOMCONNONCCOMCONNONCCOMCON74 7873 7772 7671 7524V~ 24V~24V~0 24V~0COMB COMBCOMA COMACross connector (can be removed, as desired)Actuator 1Fig. 79 Terminal assignment and internal connections offloating output moduleTer-minal Signal Comment71, 75 COM a 2-wire communication bus (LON/Panel Bus)72, 76 COM b 2-wire communication bus (LON/Panel Bus)73, 77 24 V~ Power supply74, 78 24 V~0 Power supply11 REL1 N.O. Floating relay 1 N.O. contact12 REL1 N.C. Floating relay 1 N.C. contact13 R1 COM Floating relay 1 common contact14 R1 COM For connection of floating relay 1 commonvia cross connector*21 REL2 N.O. Floating relay 2 N.O. contact22 REL2 N.C. Floating relay 2 N.C. contact23 R2 COM Floating relay 2 common contactACTUATOR 124 R2 COM For connection of floating relay 2 commonvia cross connector*31 REL3 N.O. Floating relay 3 N.O. contact32 REL3 N.C. Floating relay 3 N.C. contact33 R3 COM Floating relay 3 common contact34 R3 COM For connection of floating relay 3 commonvia cross connector*41 REL4 N.O. Floating relay 4 N.O. contact42 REL4 N.C. Floating relay 4 N.C. contact43 R4 COM Floating relay 4 common contactACTUATOR 244 R4 COM For connection of floating relay 4 commonvia cross connector*51 REL5 N.O. Floating relay 5 N.O. contact52 REL5 N.C. Floating relay 5 N.C. contact53 R5 COM Floating relay 5 common contact54 R5 COM For connection of floating relay 5 commonvia cross connector*61 REL6 N.O. Floating relay 6 N.O. contact62 REL6 N.C. Floating relay 6 N.C. contact63 R6 COM Floating relay 6 common contactACTUATOR 364 R6 COM For connection of floating relay 6 commonvia cross connector*25 Shield connection (functional earth),internally connected to the DIN rail* Do not connect by wire!Table 57 Description of floating output module terminalsManual OverridesThe floating output module is equipped with manualoverrides: one rotary knob for each floating output.These manual overrides can manually be set to either"Auto" or "0 … 100 %" (infinitely adjustable).1 2 3 HoneywellAUTO0!A A A100Fig. 80 Manual overrides (rotary knobs)NOTICEDamage to the electronic module!► Do not use a tool to adjust the rotary knobs.► Do not use excessive force. Adjust only by hand.AutoIn this setting, the signal provided by the respective floatingoutput (R1 + R2 or R3 + R4 or R5 + R6) and the condition(ON/OFF) of the respective pair of status LEDs both followthe commanded output signal.Override (0…100 %)When a manual override is set to values in the range of"0…100 %", the respective floating output will drive to theset position. The runtime depends upon the actuator runtimeconfigured in CARE an on the actual position.Status LEDsThe respective pair of status LEDs will display the following:Actuator 1Mode LEDClosing Opening NotmovingGreen LED ON OFF OFFAutoRed LED OFF ON OFFGreen LED Flashing OFF FlashingOverrideRed LED OFF Flashing FlashingTable 58 LED behavior (for e.g., floating output 1)