Excel 800 LION57 EN1B-0375GE51 R0308Floating Output ModuleFeatures• Type: CLIOPR825A Floating Output Module• Housing: light gray• Floating outputs sufficient for driving up to 3 floatingactuators• Manual overrides and 3 corresponding pairs of statusLEDsIn the event of communication problems, the 3 floatingoutputs will move to the safety positions you haveconfigured in CARE, see floating output point description inthe CARE – User Guide, 74-5587/EN2B-0182GE51.Fig. 78 CLIOPR825A Floating Output Module withterminal socketLegend1 Service button S12 Hex switch S23 Manual overrides4 Status LEDs4 Service LED5 Power LEDFunctionality of service LED and power LED: see Table 74to Table 76 on page 72 and following.WARNINGRisk of electric shock or equipment damage!Low voltage and line voltage must not be wired withinthe same relay block.► Wire low voltage e.g., to relay block 1 and line voltage torelay block 2 or vice versa. In this case the short crossconnectors must be used, see Table 5 on page 8.NOTICERisk of malfunction!Cross connectors may only be used if the same voltageis used on all relays they connected.► Do not use a cross connector if different voltages areused on the relays.E.g., use a short cross connector for relay block 1 withline voltage and no cross connector for relay block 2 with12 V low voltage for relay 4 and 24 V low voltage forrelays 5 and 6.Permissible loadsMax. load Min. loadPer relayoutputmodule (total)19…250 VACcurrent at cos φ ≥ 0.6: 12 A1…29 VDC12 A resistive, 3 A inductive–Per normallyopen contact19…250 VACcurrent at cos φ ≥ 0.6: 4 A)1…29 VDC4 A resistive, 1 A inductive50 mWPer normallyclosedcontact19…250 VACcurrent at cos φ ≥ 0.95: 2 A,current at cos φ ≥ 0.6: 1 A1…29 VDC4 A resistive, 1 A inductive50 mWTable 56 Permissible loads of floating output modulesNotes• In the case of voltages above 30 VAC/DC and if inductivecomponents are to be connected to relays switchingmore often than once every 2 minutes, these com-ponents must be prevented from causing harmfulinterference to radio or television reception (conformancewith EN 55014).• Max. voltage for UL 864-compliant applications is 24 V.