EXCEL CARE CONTROL ICONS ALPHABETIC REFERENCE41 74-5577–33 (US)EN2B-0184 GE51 R0518 (Europe)Data Transfer / IDTFunction Transfer a value from one control icon to other icons or points.Copies the input to all outputs.I/O Dialog BoxExcel Web / Excel Web IIInput One input, required. Any input point type or control icon can be an input.Output One to five outputs (Excel Web / Excel Web II: one to 32 outputs), one required.Outputs can connect to any output point (analog or digital, physical or pseudo) or tothe input of other control icons (except another IDT). An IDT cannot be an input toanother IDT.The first output type determines all other output types. For example, if the firstoutput connects to an analog point, all other outputs must connect to an analogpoint (Not for Excel Web / Excel Web II).Output Conversion If the input and output types are mismatched, IDT converts the input signal to theappropriate output signal. For example, if the input is an analog point and one of theoutputs is a digital point, IDT converts the analog signal to the proper digital signal.Conversion TableIDT InputTypeIDT OutputTypeConversion AlgorithmAI AO output = input (only type is changed)AI DO if the input < 0.5, output is 0if the input > 0.5, output is 1DI AO output = input (only type is changed)DI DO output = input (only type is changed)Still valid for XL WebAI is an analog input (physical, pseudo, or flag).AO is an analog output (physical, pseudo, or flag).DI is a digital input (physical, pseudo, or flag).DO is a digital output (physical, pseudo, or flag).Internal Parameters None.