EXCEL CARE CONTROL ICONS ALPHABETIC REFERENCE227 74-5577–33 (US)EN2B-0184 GE51 R0518 (Europe)Switching Logic/Rows Each input row consists of the following columns:Input Name = name of the rowActual Value = value which should be comparedCond. = relation between Actual Value and Comparison ValueComparison Value = reference valueHysteresis = deadband between Actual Value and Comparison ValueDelay = time delay of the row validityCase = Every selected Switch Case is displayed in the Switching logic listbox. Foreach Switch Case, it can be decided which row have to be TRUE (1),FALSE (0) or don't care (-) to make the case become TRUE.The rows have an AND relation to each other!Cond. choose between one of the following conditions to compare Actual Value andComparison Value:> greater than>= greater than or equal== equal (to be used for binary or multistage Datapoints)!= not equal (to be used for binary or multistage Datapoints)< less than<= less then or equalTangens (Excel Web / Excel Web II)Function Calculate the tangens function of X. Input value must be in radian.I/O Dialog BoxInput One analog input (X). Value in radian (–π/2 to π/ 2)Output One analog output (Y). Range: –∞ to ∞.Internal Parameters None.