7-6 C70 Capacitor Bank Protection and Control System GE Multilin7.1 COMMANDS 7 COMMANDS AND TARGETS77.1.3 VIRTUAL INPUTSPATH: COMMANDS VIRTUAL INPUTSThe states of up to 64 virtual inputs are changed here. The first line of the display indicates the ID of the virtual input. Thesecond line indicates the current or selected status of the virtual input. This status will be a state off (logic 0) or on (logic 1).7.1.4 CLEAR RECORDSPATH: COMMANDS CLEAR RECORDSThis menu contains commands for clearing historical data such as the event records. Data is cleared by changing a com-mand setting to “Yes” and pressing the ENTER key. After clearing data, the command setting automatically reverts to “No”.7.1.5 SET DATE AND TIMEPATH: COMMANDS SET DATE AND TIMEThe date and time can be entered on the faceplate keypad. The time setting is based on the 24-hour clock. The completedate, as a minimum, must be entered to allow execution of this command. The new time and date take effect when theENTER key is pressed.When the relay is synchronizing to an external time source such as PTP, IRIG-B, or SNTP, the manually entered time isover-written.The timescale of the entered time is local time, including daylight savings time where and when applicable. COMMANDS VIRTUAL INPUTSVirt Ip 1OffRange: Off, OnVirt Ip 2OffRange: Off, On↓MESSAGE Virt Ip 64OffRange: Off, On COMMANDS CLEAR RECORDSCLEAR USER FAULTREPORTS? NoRange: No, YesCLEAR EVENT RECORDS?NoRange: No, YesCLEAR OSCILLOGRAPHY?NoRange: No, YesCLEAR DATA LOGGER?NoRange: No, YesCLEAR UNAUTHORIZEDACCESS? NoRange: No, YesCLEAR DIRECT I/OCOUNTERS? NoRange: No, Yes. Valid only for units with Direct Input/Output module.CLEAR ALL RELAYRECORDS? NoRange: No, Yes COMMANDS SET DATE AND TIMESET DATE AND TIME:2000/01/14 13:47:03(YYYY/MM/DD HH:MM:SS)