Display Code* LED Code Relais switches**Possible cause Reaction of Controllerinternal Opera-tion Fault AdjustmentLmt Offset 1AL - 0 selecta-bleActual value exceeds set-pointDevice continues working un-changedCheck setting and sensorLmt Offset 2AL - 0 selecta-bleActual value drops belowsetpoint and set offsetSensor 1Msg or.AL* 6 0 selecta-bleFor Sensor 1 / Sensor 2Interruption / short circuitin the sensor leads or sen-sor values measured areoutside measuring rangeThe device works with minimalor maximum modulation de-pending on whether there is ashort-circuit or an interruption,and on the programmed modeof operation.Check sensorSensor 2*Code: Err = Error Al = Alarm Msg = Message** Relay function in factory setting0 = switching status retained1 = switching status changes13 Function extension and version of softwareSoftware D1334A, display version menu group Start under IcontrolVersion Date Function from new version2.25 19.02.09 Setting: change from “%” to “Hz” for following settings: Set Intern 1/2, Min. Speed, Max.Speed, Speed manual.2.28 03.09.09 Start: Motor OFF / ON, version nummer internal motor controllerModbus: readout serial number via Modbus possible.2.31 12.01.10 Start: New menu language Czech2.36 15.06.11 Motor Setup: Overmodulation OFF / ON2.3715.05.12 Base setup: additional Mode 1.02Setting: limitation “Min. Speed” - “Max. Speed”Controller Setup: additional group control 3 and 4 via relaysIO Setup: new function |12K|, |13K| for K1...K4Operating Instructions Icontrol – model series FXDM Function extension and version of softwareL-BAL-E036-GB 1422 Index 008 Part.-No. 00154773-GB87/96