9.9.7.2 Control group 2/3/4 via relaisGroup 2 ON valueGroup 2 ON valueSwitch-on value for Group2Setting range: 0 - 100 %Factory setting: 50 % *OFF Value Group2OFF Value Group2Switch-off value for group2Setting range: 0 - 100 %Factory setting: 45 % *nmin at Group2nmin at Group2Minimum Value for Group2Setting range: 0 - 100 %Factory setting: 20 % *When more than two groups add-on module necessary type Z-Modul-B (Part.-No. 380052).Group 3 ON valueGroup 3 ON valueSwitch-on value for Group3Setting range: 0 - 100 %Factory setting: 70 % *OFF Value Group3OFF Value Group3Switch-off value for group3Setting range: 0 - 100 %Factory setting: 65 *nmin at Group3nmin at Group3Minimum Value for Group3Setting range: 0 - 100 %Factory setting: 30 % *Group 4 ON valueGroup 4 ON valueSwitch-on value for Group4Setting range: 0 - 100 %Factory setting: 85 % *OFF Value Group4OFF Value Group4Switch-off value for group4Setting range: 0 - 100 %Factory setting: 80 % *nmin at Group4nmin at Group4Minimum Value for Group4Setting range: 0 - 100 %Factory setting: 40 % ** As long as in IO Setup “K Function” not programmed display: |- - - -|Higher settings must be chosen for subsequent groups. Switch-off value of the group always belowthe switch-on value.Function• Group 1 continuously controlled by the device’s “Master” power unit ( motor connection).• Other motors are switched directly to line voltage by contactors via the relay outputs “K1..K4”.Depending on the additional groups count the function for the relays must be programmed (IOSetup / K.. Function: |8K| = group 2, |12K| = group 3, |13K| = group 4). Keep the order!Operating Instructions Icontrol – model series FXDM ProgrammingL-BAL-E036-GB 1422 Index 008 Part.-No. 00154773-GB48/96