12.2 Messages and trouble shootingA momentary pending alarm or error message is indicated by a blinking indicator and appearsalternately with the standard display.Operating conditions are indicated by the internal status LED with flashing code.internal State LED11.02.2009v_flash_explain.VSD3 x2 xONOFF4 x5 x6 x1 x7 x8 x9 xDisplay Code* LED Code Relais switches**Possible cause Reaction of Controllerinternal Opera-tion Fault AdjustmentOFFLine voltage available?Unit switch OFF and automati-cally ON when the voltage hasbeen restored1 1 0No enable Switch OFF by external contact(function |1D| = enable pro-grammed for Digital In)Factory sett.AL - 0 1Controller did a factory set-ting automatically (e.g. incase of faulty parameterdata).Warning message:Operation with factory settingEEP errorAL - 0 1 fault EEP damaged works with defaultsEEP CorruptionAL - 0 1EEP data incorrectlycontroller runs with the readsettingsMC Bootload AL - 0 1Fault bootload process ofthe motor controller. I.e.the motor controller pro-gram could not be loadedor started.Fault indication, cold start(reset) of the control unitMC CommunicationAL - 1 1Communication fault be-tween control unit andpower unit Fault indication, cold start(reset) of the control unitDataset errorAL - 0 1Error in the protocol mem-ory (event log) Only warning messageOperating Instructions Icontrol – model series FXDM Events / Fault signalsL-BAL-E036-GB 1422 Index 008 Part.-No. 00154773-GB84/96