PropertyObject TypeDevice AnalogInput AnalogOutput AnalogValue BinaryOutput BinaryOutput BinaryValueInactive_Text – – – – Yes Yes YesActive_Text – – – – Yes Yes Yes<1> For Commandable Object Instances only.u Analog Input ObjectsTable C.4 Analog Input ObjectsObject ID Object Name ModbusAddress Precision Range Units PV AccessAI1 Analog Input 1 Level 004EH XXXX.X – % RAI2 Analog Input 2 Level 004FH XXXX.X – % RAI3 Not used AI3 – – – – –AI4 Not used AI4 – – – – –AI5 Not used AI5 – – – – –AI6 Display Format o1-03 0502H XXXXX – – RAI7 Scale Format b5-20 01E2H XXXXX – – RAI8 Inverter Model o2-04 0508F XXXXX – – RAI9 Rated Current n9-01 05D0H XXXX.X – Amps RAI10 Motor Current UB-01 8780H XXXX.X – Amps RAI11 Contactor Voltage 8790H XXXXX – Volts Ru Analog Output ObjectsTable C.5 Analog Output ObjectsObject ID Object Name ModbusAddress Precision Range Units PV AccessAO1 Analog Output 1 Level 0007H XXXX.X 0 to 100.0 % CAO2 Analog Output 2 Level 0008H XXXX.X 0 to 100.0 % Cu Analog Value ObjectsTable C.6 Analog Value ObjectsObject ID Object Name ModbusAddress Precision Range Units PV AccessAV1 Operation Cmd 0001H – – – CAV2 Frequency Cmd 8401H XXX.XXDepends ono1-03 0.00 to 600.00 HzDepends on o1-03 CAV3 PI Setpoint Cmd 0006H XXX.XX -100.00 to 100.00 % CAV4 MF Output Cmd 0009H – – – CAV5 Reference Select Cmd 000FH – – – CAV6 Drive Status 0020H – – – RAV7 Fault Details 0021H – – – RAV8 Data Link Status 0022H – – – RAV9 Frequency Reference 0040H XXX.XXDepends ono1-03 – HzDepends on o1-03 RAV10 Output Frequency 0041H XXX.XXDepends ono1-03 – HzDepends on o1-03 RAV11 Output Voltage 0045H XXXX.X – Volts RAV12 Output Current 0026H XXXX.X – Amps RC.6 BACnet Objects Supported368 YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual