u E2: Motor 1 ParametersThese parameters contain the motor data needed for motor 1. Enter the motor data into these parameters when Auto-Tuningcannot be performed.n E2-01: Motor Rated CurrentProvides motor control, protects the motor, and calculates torque limits. Set E2-01 to the full load amps (FLA) stamped onthe motor nameplate.No. Parameter Name Setting Range DefaultE2-01 Motor Rated Current 10% to 200% of the driverated current Determined byo2-04Note: The number of decimal places in the parameter value depends on the drive model. Refer to Defaults by Drive Model on page 356 fordetails.n E2-03: Motor No-Load CurrentSet the no-load current for the motor in amperes when operating at the rated frequency and the no-load voltage. The drive setsE2-03 during the Auto-Tuning process (Rotational Auto-Tuning and Stationary Auto-Tuning 1, 2). The motor no-load currentlisted in the motor test report can also be entered to E2-03 manually. Contact the motor manufacturer to receive a copy of themotor test report.No. Parameter Name Setting Range DefaultE2-03 Motor No-Load Current 0 to [E2-01](unit: 0.01 A)Determined byo2-04Note: The number of decimal places in the parameter value depends on the drive model. This value has two decimal places (0.01 A) if the driveis set for a maximum applicable motor capacity up to and including 11 kW, and one decimal place (0.1 A) if the maximum applicable motorcapacity is higher than 11 kW.5.6 E: Motor ParametersYASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual 1495 Programming