ICON5 / ICONXFlow Meter Setup• If a flow meter will be used in this application,continue with step 1.• If a flow meter will not be used in this application,continue with step 6.To set the Flow Meter, follow these steps:1. Push Menu, System, Data, and Flow/Hours todisplay the Flow/Hours screen. See Figure 32-1.2. Select the Flow Multiplier field. See Figure 32-1.3. Using the numeric keypad, enter the manufactur-er’s recommended pulse multiplier value in eithergallons per pulse or liters per pulse, dependingon the unit of measure.4. To enable the Low Flow Limit, select the LowFlow Limit field to open the numeric keypad.5. Enter the minimum flow rate value into the nu-meric keypad and push Enter to retain the value.The range is 1-999 gpm (lpm).NOTE• The Low Flow Limit will automatically beenabled when a valid number is enteredinto the keypad, this will be indicatedwhen the Low Flow Limit checkbox be-comes checked. A value of 0 disables theLow Flow Limit.5612 3 4Figure 32-1 1. Menu2. System3. Data4. Flow/Hours5. Flow Multiplier6. Low Flow Limit Field32Setup