5.5 GROUP 3.5: I/O CONFIGURATIONTable 14: Digital input settingsIndex Parameter Default ID DescriptionP3.5.1.1 Control Signal 1 A DigIN SlotA.1 403 Start signal 1 when the control placeis I/O A (FWD).P3.5.1.2 Control Signal 2 A DigIN SlotA.2 404 Start signal 2 when the control placeis I/O A (REV).P3.5.1.3 Control Signal 1 B DigIN Slot0.1 423 Start signal 1 when the control placeis I/O B.P3.5.1.4 Control Signal 2 B DigIN Slot0.1 424 Start signal 2 when the control placeis I/O B.P3.5.1.5 I/O B Control Force DigIN Slot0.1 425 CLOSED = Force the control place toI/O B.P3.5.1.6 I/O B Reference Force DigIN Slot0.1 343 CLOSED = I/O reference B (P3.3.4)gives the frequency reference.P3.5.1.7 External Fault Close DigIN SlotA.3 405 OPEN = OKCLOSED = External faultP3.5.1.8 External Fault Open DigIN Slot0.2 406 OPEN = External faultCLOSED = OKP3.5.1.9 Fault Reset Close DigIN SlotA.6 414Resets all active faults when thestate of the digital input is changedfrom 0 to 1 (rising edge).P3.5.1.10 Fault Reset Open DigIN Slot0.1 213Resets all active faults when thestate of the digital input is changedfrom 1 to 0 (falling edge).P3.5.1.11Run Enable DigIN Slot0.2 407You can set the drive in Ready state,when this is ON.P3.5.1.12Run Interlock 1 DigIN Slot0.2 1041The drive can be ready, but the startis not possible when the interlock ison (Damper interlock).P3.5.1.13Run Interlock 2 DigIN Slot0.2 1042As above.PARAMETERS MENU VACON · 6724-HOUR SUPPORT +358 (0)201 212 575 · EMAIL: VACON@VACON.COM 5