P3.5.1.11 RUN ENABLE (ID 407)When the contact is OPEN, the start of the motor is disabled.When the contact is CLOSED, the start of the motor is enabled.To stop, the drive obeys the value of P3.2.5 Stop Function. The follower drive will alwayscoast to stop.P3.5.1.12 RUN INTERLOCK 1 (ID 1041)P3.5.1.13 RUN INTERLOCK 2 (ID 1042)If an interlock is active, the drive cannot start.You can use this function to prevent the start of the drive when the damper is closed. If youactivate an interlock during the operation of the drive, the drive stops.P3.5.1.15 PRESET FREQUENCY SELECTION 0 (ID419)P3.5.1.16 PRESET FREQUENCY SELECTION 1 (ID420)P3.5.1.17 PRESET FREQUENCY SELECTION 2 (ID421)To apply Preset frequencies 1 to 7, connect a digital input to these functions with theinstructions in Chapter 9.5.1 Programming of digital and analogue inputs. See more data inTable 59 The selection of preset frequencies when P3.3.10 = Binary coded and also in Table 12Control reference settings and Table 14 Digital input settings.9.5.3 ANALOGUE INPUTSP3.5.2.2 AI1 SIGNAL FILTER TIME (ID 378)This parameter filters out disturbances in the analogue input signal. To activate thisparameter, give it a value that is bigger than 0.NOTE!A long filter time makes the regulation response slow.PARAMETER DESCRIPTIONS VACON · 14124-HOUR SUPPORT +358 (0)201 212 575 · EMAIL: VACON@VACON.COM 9