Table 14: Digital input settingsIndex Parameter Default ID DescriptionP3.5.1.14 Motor Preheat ON DigIN Slot0.1 1044OPEN = No action.CLOSED = Uses the DC current of themotor preheat in Stop state. Usedwhen the value of P3.1.2.5 is 2.P3.5.1.15Preset Frequency Selection 0 DigIN SlotA.4 419A binary selector for preset speeds(0-7). See Table 12 Control referencesettings.P3.5.1.16Preset Frequency Selection 1 DigIN SlotA.5 420A binary selector for preset speeds(0-7). See 5.3 Group 3.3: Control refer-ence settings.P3.5.1.17Preset Frequency Selection 2 DigIN Slot0.1 421A binary selector for preset speeds(0-7). See Table 12 Control referencesettings.P3.5.1.18 Timer 1 DigIN Slot0.1 447The rising edge starts Timer 1 thatwas programmed in Group 3.11:Timer functions.P3.5.1.19 Timer 2 DigIN Slot0.1 448 See above.P3.5.1.20 Timer 3 DigIN Slot0.1 449 See above.P3.5.1.21 Disable Timer Function DigIN Slot0.1 1499This digital input signal controls alltimer functions (for example, Inter-vals 1-5 and Timers 1-3).CLOSED = Disables the Timer func-tions and resets timers.OPEN = Enables the Timer functions.P3.5.1.22 PID1 Setpoint Boost DigIN Slot0.1 1047 OPEN = No boostCLOSED = BoostP3.5.1.23 PID1 Select Setpoint DigIN Slot0.1 1046 OPEN = Setpoint 1CLOSED = Setpoint 2P3.5.1.24 PID2 Start Signal DigIN Slot0.2 1049OPEN = PID2 in stop modeCLOSED = PID2 regulatingThis parameter has no effect if thePID2 controller is not enabled in theBasic menu for PID2VACON · 68 PARAMETERS MENU5 TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205