9.5.4 DIGITAL OUTPUTSP3.5.3.2.1 BASIC RO1 FUNCTION (ID 11001)Table 60: The output signals through RO1Selectionnumber Selection name Description0 Not used The output is not used.1 Ready The AC drive is ready to operate.2 Run The AC drive operates (the motor runs).3 General fault A fault trip occurred.4 General fault inverted A fault trip did not occur.5 General alarm6 Reversed The reverse command is given.7 At speed The output frequency has become the same as the set fre-quency reference.8 Motor regulator activated One of the limit regulators (for example current limit or tor-que limit) is activated.9 Preset Frequency active The selection of preset frequency was made with digital inputsignals.10 Keypad control active The selection is keypad control (the active control place iskeypad).11 I/O control B active The selection is I/O control place B (the active control placeis I/O B).12 Limit supervision 1 The limit supervision activates if the signal value goes belowor above the set supervision limit (P3.8.3 or P3.8.7).13 Limit supervision 214 Start command active Start command is active.15 Reserved16 Fire mode ON17 RTC timer 1 control Time channel 1 is in use.18 RTC timer 2 control Time channel 2 is in use.19 RTC timer 3 control Time channel 3 is in use.20 FB Control WordB 1321 FB Control WordB 14PARAMETER DESCRIPTIONS VACON · 14324-HOUR SUPPORT +358 (0)201 212 575 · EMAIL: VACON@VACON.COM 9